630.x Drive defective
Description
An internal error of the ACOPOSmulti device has occurred.
Remedy
If the error occurs again after rebooting of the machine (power supply ON/OFF), the device must be replaced.
9002, 9003: Heat sink temperature not within the specified tolerance.
- The measured temperature of the heat sink is colder than -20 °C (9002) or higher than 120 °C (9003). Check the cooling system.
- If 9002 occurs and the heat-sink temperature is suspected to be in the valid range, this can be an indication of condensation/condensed water in the device. Shut down the machine immediately and make sure the devices are in a dry spot (dry using tools / switch on the air conditioner and close the cabinet doors).