838.x Monitor: Input signal out of range


Description

The monitor analog input signal is out of range. The sensor signal can be adjusted by means of reset pulse (Reset=24 V). The monitor node automatically sets the reset signal in Machine OFF when the analog input signal shows a certain deviation from 0 V. The analog input signal can be checked at the corresponding connectors on the measuring card.

Remedy

  1. Weld a new can-body series and check whether an error message is issued (if not, reset was successful).
  2. Check whether the measuring bridge is correctly connected (connector in calibrating tool).
  3. Check wiring and power supply of the entire sensor system (including the interface card).
  4. Measure the analog input signal and, if possible, the reset pulse.
  5. If the analog input signal is approx.- 12V, it indicates an interruption outside the monitor box or a defective interface card.