instruction for C6920 industrial pc
Summary
All Beckhoff control units are equipped with a UPS to ensure the proper shutdown of the control IPC.
However, this only works if the battery is in perfect condition to prevent data loss and ensure the
flawless operation of the control system. The battery module for the UPS must be replaced every 5
years.
To order a new battery please contact spares.canman@soudronic.com.
Battery type C9900-U330 Order number 013230
Preconditions
- Allen key 4
- Screw driver 1
- C9900-U330 replacement battery
Remedy
- Switch off the main power of machine.
- Wait until the IPC has shut down completely.
- Disconnect the wires on battery terminal block.
- Hold the battery by hand, unscrew the four screws, and remove it from the rail.
- Place the new battery pack on the DIN rail and tighten the four screws.
- Connect the wires to new battery. Attention! The battery is already loaded! Do not make short circuit! Take care for correct + / - connection.
- After double check the wiring switch on the main power of machine.