i/o terminals are not active
Description:
Some Beckhoff i/o terminals are not active and status LED's are off, control does not respond to commands.
Remedy:
- The 24Vdc supply of the EK1100 coupler or the EL9410 intermediate supply terminal is missing.
- Check all connections and fuses.
- Check all connections and fuses.
- Voltage is too low.
- Measure voltage.
- Measure voltage.
- Bad contact between the terminals.
- Switch off the main power and remove the terminals.
- Clean the contact between the terminals.
- Defective EL9410 intermediate supply terminal.
- Exchange terminal.
- Defective EK1100 coupler.
- Exchange coupler.
- Exchange coupler.