Views:

i/o terminals are not active


Description:

Some Beckhoff i/o terminals are not active and status LED's are off, control does not respond to commands.

Remedy:

  • The 24Vdc supply of the EK1100 coupler or the EL9410 intermediate supply terminal is missing.
    • Check all connections and fuses.
       
  • Voltage is too low.
    • Measure voltage.
       
  • Bad contact between the terminals.
    • Switch off the main power and remove the terminals.
    • Clean the contact between the terminals.
       
  • Defective EL9410 intermediate supply terminal.
    • Exchange terminal.
  • Defective EK1100 coupler.
    • Exchange coupler.

 

Related Products: CM 16