Issue on single slitter with Siemens PLC


Problem:

  • Error message „Magnet belt not down” displayed on HMI.
  • Arrow buttons „Up” and „Down” for magnet belt are not visible anymore.
    • Magnet belt does only exist on the second table on the duplex slitter.

Causes & Resolutions:

Arrow button „Up” for magnet belt may be visible for a brief time and pushed during startup of panel.

Delete error message:

  1. Login with canman user → Contact CANMAN for password
  2. Go to Setup
  3. Change the function Single slitter to OFF (See attached picture)
  4. Go back to the main screen.
    • The up and down button for magnet belt will be visible.
  5. Push and hold the arrow button down for magnet belt until the error message “Magnet belt not down“ disappears.
  6. Go back to the canman settings and set the function “Single slitter” back to ON.