Node Pulsar has wrong Poland
Issue:
(Unicontrol machines with Pulsar capable of automatic download.)
If a PULSAR that is capable of automatic download is installed in an UNICONTROL system which is not capable of automatic PULSAR download, the GCC will send a fault Message “Node Pulsar has wrong Poland”.
This can only happen if you install a Pulsar from a newer UNICONTROL machine to an older system.
Example:
Remedy:
The Pulsar has to be set to “Not download capable”
Go to Menu -> Service -> Operator Lever
Set password to 0035
Go to Menu -> Pulsar Config -> Allow CAN configure
Set Val: to Off
Exit the Pulsar Menu and Reboot the Machine.