Set the switching pressure SP with two teach pressures TP1/TP2 on MS6-SV-1/2-C


Situation:

The defective pressure switch needs to be replaced on the maintenance unit.

Procedure:

After replacing the unit, the set points need to be set. The set points are machine specific and found in the manual. 

  • Switch on the operating voltage.
  • Apply teach pressure TP1 (high pressure) to MS6-SV-1/2-C.
  • Press and hold the Edit button for at least 2 seconds.
          LED flashes.
     
  • Release the Edit button.
         Teach pressure TP1 is stored.
     
  • Apply teach pressure TP2 (lower pressure) to MS6-SV-1/2-C.
     
  • Press the Edit button until the LED stops flashing.
     
  • Release the Edit button.
         Teach point TP2 is stored.
     
  • Ensure power supply for at least 10 seconds.
     
  • Test in test run whether MS6-SV-1/2-C switches as desired. The LED lights when the switching signal is output.

 